| CLICK ON THE LINK BELOW TO ACCESS THE TEST REPORT ↓ ↓ ↓ ↓ | PART # | D.F.T. | MAXIMUM FOAM THICKNESS | ESTIMATED COVERAGE RATE |
2 lb Closed Cell Foam to meet IBC chapter 8 interior finish and plenum requirements |
F10E | 16 mils | 4 ½ inches of 2 lb SPF insulation | 70-80 |
Bayseal CC 2lb Foam |
BMS-TC | 14 mils | 7 ¼ inches foam in walls & 9 ¼ inches in ceiling of 2lb SPF | 80-90 |
Demilec Heatlok Soy™
|
TB-200 Primer TB-200 |
4 mils 8 mils |
9 ¼ inches foam in walls & 11 ¼ inches in ceiling of 2lb SPF | 160-170 105-120 |
.5 lb Demilec Sealection™ |
F10E | 14 mils | 5 ½ inches & 10 inches of .5lb SPF insulation | 75-85 |
Gaco Green 052 |
F10E | 14 mils | 5 ¼ inches foam in walls & 9 ¼ inches in ceiling of .5lb SPF | 65-80 |
JM Corbond III 2lb Foam in attics, attic floors, and crawl spaces. |
F1E | 17 mils | 12' x 8' wood studded room with 2'x 6'walls and 2 x 10' ceiling with FIRESHELL® Intumescent Coating over 8 inches in walls, 10 inches in ceiling of 2lb SPF | 70-80 |
COMPOSITE FIBERGLASS encapsulated 2lb Foam |
F10E | 15 mils | FIRESHELL® Intumescent Coating over 4 x 8 x2" thick composite fiberglass (encasing 2lb foam) wall panels attached together with bolts | 85-95 |
FIRESHELL® SYSTEM
|
F1E F10E |
4 mils 8 mils |
9 ½ inches foam in walls & 11 ½ inches in ceiling of 2lb SPF | 160-170 105-120 |
| ICC AC377 approved Ignition Barriers | PART # | PRODUCT | D.F.T. | DESCRIPTION | SUBSTRATE | RESULTS |
| NFPA 286 with Acc. Criteria AC377 appendix X on Closed Cell Sprayfoam. | F1E | FIRESHELL® | 8 mils | Flame spread and heat release using Full Scale Room Corner over Closed Cell sprayfoam | 2# closed cell spray foam (9 1/2" walls, 11 1/2" ceiling) with F1E coating | Meets NFPA 286 with Acc. Criteria AC377 appendix X |
| ER report with Acceptance Criteria AC377 appendix X on Closed Cell Sprayfoam | F1E | FIRESHELL® | 17 mils | Flame spread and heat release using Full Scale Room Corner over Closed Cell sprayfoam | 2# closed cell spray foam (8" walls, 10" ceiling) with F1E coating | Meets NFPA 286 with Acc. Criteria AC377 appendix X |
| NFPA 286 with Acc. Criteria AC377 appendix X on Open Cell Sprayfoam | IB4 | FIRESHELL® | 8 mils | Flame spread and heat release using Full Scale Room Corner over Open Cell Sprayfoam | 1/2# open cell spray foam (7 1/2" walls, 11 1/2" ceiling) with IB 4 coating | Meets NFPA 286 with Acc. Criteria AC377 appendix X |
| NFPA 286 with Acc. Criteria AC377 appendix X on SOY FOAM | IB4 | FIRESHELL® | 8 mils | Flame spread and heat release using Full Scale Room Corner over Open Cell Soy Foam | 3/4# open cell soy foam (9 1/2" walls, 11 1/2" ceiling) with IB4 coating | Meets NFPA 286 with Acc. Criteria AC377 appendix X |
| NFPA 286 with Acc. Criteria AC377 appendix X on OPEN CELL FOAM | IB4 | FIRESHELL® | 8 mils | Flame spread and heat release using Full Scale Room Corner over Open Cell Foam | 1/2# open cell foam (9 1/2" walls, 11 1/2" ceiling) with IB4 coating | Meets NFPA 286 with Acc. Criteria AC377 appendix X |
| ICC AC377 approved Ignition Barriers | PART # | PRODUCT | D.F.T. | DESCRIPTION | SUBSTRATE | RESULTS |
| NFPA 286 with Acc. Criteria AC377 appendix A on CLOSED CELL FOAM | F1E | FIRESHELL® Ultra | 10 mils | Flame spread and heat release using Full Scale Room Corner over Closed Cell Foam | 2# closed cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room | superior to plywood, room meets AC377 |
| NFPA 286 with Acc. Criteria AC377 appendix A on OPEN CELL FOAM | F1E | FIRESHELL® Ultra | 10 mils | Flame spread and heat release using Full Scale Room Corner over Open Cell Foam | 1/2" open cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room | superior to plywood, room meets AC377 |
| NFPA 286 with Acc. Criteria AC377 appendix A on OPEN CELL FOAM CRAWL SPACES | F1E | FIRESHELL® Ultra | 10 mils | Flame spread and heat release using Full Scale Room Corner over open cell foam | 3/4# open cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room | superior to plywood, room meets AC377 |
| NFPA 286 with Acc. Criteria AC377 appendix A on OPEN CELL FOAM CRAWL SPACES | F10E | FIRESHELL® | 12 mils | Flame spread and heat release using Full Scale Room Corner over Open Cell Foam | 1/2# open cell foam (5 1/2" walls, 10" ceiling) with F10E compared to 1/4" plywood room | superior to plywood, room meets AC377 |
| NFPA 286 with Acc. Criteria AC377 appendix A on CLOSED CELL FOAM CRAWL SPACES | F10E | FIRESHELL® | 14 mils | Flame spread and heat release using Full Scale Room Corner over closed cell foam | 2# closed cell foam(9" walls, 13" ceiling) with F10E compared to 1/4" plywood room | superior to plywood, room meets AC377 |
| NFPA 286 with Acc. Criteria AC377 appendix A BASELINE test | NA | NA | NA | BASELINE test: Flame spread and heat release using Full Scale Room Corner over Open Cell Foam | Foam (7" walls, 11" ceiling) under 1/4" plywood room | Plywood room fails at 4:29 min |