NFPA 286 |
Product |
Description |
Substrate |
Results |
Full Scale Room Corner over Closed Cell Foam |
Fireshell®-F10E |
Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and
conforms to IBC 2603.9 & IRC 314.3 on a 12' x 8' wood studded room with 4
1/2" of exposed closed cell foam
|
Fireshell®Intumescent Coating over 4 1/2 inches of 2 pcf sprayfoam insulation |
No flame spread and no indication of excessive smoke |
Full Scale Room Corner over Open Cell Foam |
Fireshell®-F10E |
Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and
conforms to IBC 2603.9 & IRC 314.3 on a 12' x 8' wood studded room with 5
1/2" of exposed foam in the walls and 10" of exposed foam in the ceilings.
|
Fireshell®Intumescent Coating over 5 1/2 inches & 10 inches of 1/2 pcf
sprayfoam insulation
|
Met the IBC acceptance criteria defined in IBC 803.2.1
|
Full Scale Room Corner over Composite Fiberglass over Closed Cell Foam |
Fireshell®-F10E |
Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and conforms to IBC 2603.9 & IRC 314.3 over a composite structure composite of fiberglass encasing 2lb foam.
|
Fireshell®Fireshell® Intumescent Coating over 4 x 8 x2" thick composite fiberglass on foam wall panels attached together with bolts. |
No flame spread and no indication of excessive smoke |
ICC AC377 approved Ignition Barriers |
Product |
Description |
Substrate |
Results |
NFPA 286 with Acc. Criteria AC377 appendix A |
Fireshell® F1E 10 mil |
Flame spread and heat release using Full Scale Room Corner over Closed Cell Foam |
2# closed cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room |
superior to plywood, room meets AC377 |
NFPA 286 with Acc. Criteria AC377 appendix A |
Fireshell® F1E 10 mil |
Flame spread and heat release using Full Scale Room Corner over Open Cell Foam |
1/2" open cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room |
superior to plywood, room meets AC377 |
SWRI 99-02 w/ AC-12 Ignition Barrier test |
Flexible Fireshell® F1E (8mils) over 4” of 2lb sprayfoam |
Flame spread and Flame penetration resistance according to SWRI 99-02 ignition barrier test
|
plywood sheathed 8’ x8’ wall, 4” of 2lb PU insulation sprayfoam |
Flames never exited front or through, Exceeds AC-12 |
NFPA 286 with Acc. Criteria AC377 appendix A |
Fireshell® F1E 10 mil |
Flame spread and heat release using Full Scale Room Corner over open cell foam |
3/4# open cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room |
superior to plywood, room meets AC377 |
NFPA 286 with Acc. Criteria AC377 appendix A |
Fireshell® F10E 12 mil |
Flame spread and heat release using Full Scale Room Corner over Open Cell Foam |
1/2# open cell foam (5 1/2" walls, 10" ceiling) with F10E compared to 1/4" plywood room |
superior to plywood, room meets AC377 |
NFPA 286 with Acc. Criteria AC377 appendix A |
Fireshell® F10E 14 mil |
Flame spread and heat release using Full Scale Room Corner over closed cell foam |
2# closed cell foam(9" walls, 13" ceiling) with F10E compared to 1/4" plywood room |
superior to plywood, room meets AC377 |
NFPA 286 with Acc. Criteria AC377 appendix A |
Fireshell® F10E 19 mil |
Flame spread and heat release using Full Scale Room Corner over open cell foam |
3/4# open cell foam (5 1/2" walls, 10" ceiling) with F10E compared to 1/4" plywood room |
superior to plywood, room meets AC377 |
NFPA 286 with Acc. Criteria AC377 appendix A BASELINE test |
Standard Wood Room |
BASELINE test: Flame spread and heat release using Full Scale Room Corner over Open Cell Foam |
Foam (7" walls, 11" ceiling) under 1/4" plywood room |
Plywood room fails at 4:29 min |