FULL SCALE TESTS FOR PROTECTION OF OPEN AND CLOSED CELL SPRAYFOAM

TPR2 is a company developed to provide revolutionary products and solutions for fire, heat, thermal and safety issues that a multiple of industries face today. Our proprietary formulations, unique product compositions and rapid, custom solutions build a strong foundation for cost effective, creative, quick-response solutions to suit our customers' fire protection needs.

You will need a Username & Password to view our certification materials.
PLEASE CALL: 203-756-TPR2

NFPA 286

Product

Description

Substrate

Results

Full Scale Room Corner over
Closed Cell Foam

Fireshell®-F10E

Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and conforms to IBC 2603.9 & IRC 314.3 on a 12' x 8' wood studded room with 4 1/2" of exposed closed cell foam

Fireshell®Intumescent Coating over 4 1/2 inches of 2 pcf sprayfoam insulation

No flame spread and no indication of excessive smoke

Full Scale Room Corner over
Open Cell Foam

Fireshell®-F10E

Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and conforms to IBC 2603.9 & IRC 314.3 on a 12' x 8' wood studded room with 5 1/2" of exposed foam in the walls and 10" of exposed foam in the ceilings.

Fireshell®Intumescent Coating over 5 1/2 inches & 10 inches of 1/2 pcf sprayfoam insulation

Met the IBC acceptance criteria defined in IBC 803.2.1

Full Scale Room Corner over Composite Fiberglass over Closed Cell Foam

Fireshell®-F10E

Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and conforms to IBC 2603.9 & IRC 314.3 over a composite structure composite of fiberglass encasing 2lb foam.

Fireshell®Fireshell® Intumescent Coating over 4 x 8 x2" thick composite fiberglass on foam wall panels attached together with bolts.

No flame spread and no indication of excessive smoke


ICC AC377 approved Ignition Barriers

Product

Description

Substrate

Results

NFPA 286 with Acc. Criteria AC377 appendix A

Fireshell® F1E 10 mil

Flame spread and heat release using Full Scale Room Corner over Closed Cell Foam

2# closed cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room

superior to plywood, room meets AC377

NFPA 286 with Acc. Criteria AC377 appendix A

Fireshell® F1E 10 mil

Flame spread and heat release using Full Scale Room Corner over Open Cell Foam

1/2" open cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room

superior to plywood, room meets AC377

SWRI 99-02 w/ AC-12 Ignition Barrier test

Flexible Fireshell® F1E
(8mils) over 4” of 2lb sprayfoam

Flame spread and Flame penetration resistance according to SWRI 99-02 ignition barrier test

plywood sheathed 8’ x8’ wall, 4” of 2lb PU insulation sprayfoam

Flames never exited front or through, Exceeds AC-12

NFPA 286 with Acc. Criteria AC377 appendix A

Fireshell® F1E 10 mil

Flame spread and heat release using Full Scale Room Corner over open cell foam

3/4# open cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room

superior to plywood, room meets AC377

NFPA 286 with Acc. Criteria AC377 appendix A

Fireshell® F10E 12 mil

Flame spread and heat release using Full Scale Room Corner over Open Cell Foam

1/2# open cell foam (5 1/2" walls, 10" ceiling) with F10E compared to 1/4" plywood room

superior to plywood, room meets AC377

NFPA 286 with Acc. Criteria AC377 appendix A

Fireshell® F10E 14 mil

Flame spread and heat release using Full Scale Room Corner over closed cell foam

2# closed cell foam(9" walls, 13" ceiling) with F10E compared to 1/4" plywood room

superior to plywood, room meets AC377

NFPA 286 with Acc. Criteria AC377 appendix A

Fireshell® F10E 19 mil

Flame spread and heat release using Full Scale Room Corner over open cell foam

3/4# open cell foam (5 1/2" walls, 10" ceiling) with F10E compared to 1/4" plywood room

superior to plywood, room meets AC377

NFPA 286 with Acc. Criteria AC377 appendix A BASELINE test

Standard Wood Room

BASELINE test: Flame spread and heat release using Full Scale Room Corner over Open Cell Foam

Foam (7" walls, 11" ceiling) under 1/4" plywood room

Plywood room fails at 4:29 min

CERTIFICATIONS FOR TPR2 FIRE RETARDANT COATINGS